• Shawn Tierney commented on lesson Lesson 09: Intro to View Studio 4 years, 8 months ago

    Good morning Gary,

    Thank you for your question. Converting .MER runtime files can be quite complicated, and I do cover this in Appendix D.

    That said, here's a couple of quick notes for anyone with similar questions:

    1) Not all .MER files can be edited / restored to a project: Old versions didn't support this at all, and later versions allow you to disable conversion when making new .MER files.

    2) If you're using ViewStudio 6.1 to 9.0 on a 64bit version of Windows, you will not be able to convert restore-able pre-6.1 .MER files without the Legacy conversion tool, or the patch mentioned in the below tech note:

    https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1059820/loc/en_US

    So back to your specific question Gary, assuming you're running a pre-v10 version of ViewStudio, I would suggest running the above patch to see if it resolves the issue,

    Hope this helps,

    Shawn Tierney,
    Instructor at The Automation School